Pressure tank size / 5 gpm

Pressure tank size for a 5 gpm pump

A 5 gallon-per-minute pump needs a tank that holds 5 gallons of drawdown between cut-out and cut-in, so the motor runs at least one minute each time it starts. On a 40/60 switch that means a tank of at least 19.4 gallons total; on 30/50, 16.9; on 20/40, 14.5. The smallest Goulds HydroPro tank that clears it at 40/60 is the V60B, 19.9 gallons.

Drawdown for 1 minute
5 gal
Tank at 40/60
19.4 gal
Tank at 30/50
16.9 gal
Two-minute cycles, 40/60
38.8 gal
20/40 psi14.5 gal30/50 psi16.9 gal40/60 psi19.4 gal
Smallest total tank volume that lets a 5 gpm pump run one minute, by pressure switch setting (precharge 2 psi below cut-in).

Five gallons a minute is below every figure in Goulds' household table, which starts at 7 gpm for a one-bathroom house, but it matches the long-term well yield New York's health department suggests as a minimum.

A pump this small is common on a low-yield well, where the pump is kept small so it cannot draw the well down. Here the tank question is easy: the 19.9-gallon class clears the one-minute rule at every common setting, and a 2-minute cycle needs 29 to 39 gallons.

Tank size by switch setting

SwitchPrechargeUsable shareTank, 1-min runSmallest Goulds HydroProTank, 2-min runSmallest Goulds HydroPro
20/40 psi18 psi34.5%14.5 galV60B (19.9 gal)29 galV100 (31.8 gal)
30/50 psi28 psi29.5%16.9 galV60B (19.9 gal)33.9 galV140B (45.2 gal)
40/60 psi38 psi25.8%19.4 galV60B (19.9 gal)38.8 galV140B (45.2 gal)

Tank volumes: Goulds Water Technology (Xylem), Technical Manual TTECHWP R7, Table 1. Run time: Franklin Electric, Application • Installation • Maintenance (AIM) Manual, Submersible Systems, 60 Hz (2026) — copy published by the Nebraska Department of Water, Environment and Energy. Precharge: AMTROL, "Using an air gauge, adjust the precharge to 2 psig below the cut-in (LO) setting."

What the tank does at 40/60

At 60 psi (pump off)29.5% water5.1 galAt 40 psi (pump on)3.7% water
A 19.9-gallon tank precharged to 38 psi, drawn to scale by volume: the shaded band is the 5.1 gallons drawn off between cut-out and cut-in (Boyle's law).

The V60B holds 19.9 gallons in all. Precharged to 38 psi, it is 25.8% usable between 40 and 60 psi: 5.1 gallons, enough for 1 minutes of pump run at 5 gpm. Goulds' own table lists this tank at 5.8 gallons of drawdown "at 38/60" — the larger figure counts water drawn below the 40 psi cut-in, down to the precharge, which the pump never lets happen in use. That is why this page sizes from the switch points instead.

Why the setting changes the tank

Air in the tank is compressed as water comes in, so the share of the tank you can actually use depends on the pressures. Between 20 and 40 psi it is 34.5%; at 30/50 it is 29.5%; at 40/60 only 25.8%. Raising the switch for stronger showers therefore needs a bigger tank for the same pump — 4.9 gallons more at 5 gpm when moving from 20/40 to 40/60.

Longer cycles are easier on the motor. Franklin Electric's minimum is one minute; its starts-per-day limits (300 for single-phase motors up to 0.75 hp, 100 for single-phase motors 1 to 5.5 hp, 50 for single-phase motors 7.5 to 30 hp) are the other half of the picture. Sizing for two minutes doubles the tank and roughly halves the starts.

Other pump flows

7 gpm · 10 gpm · 14 gpm · 17 gpm · 20 gpm. Not sure of your pump's flow? The pump calculator works it out from bathrooms and depth, and the pump-by-depth pages list rated flows.