Well pump size by depth

How much pump a house needs depends on two things: the flow its bathrooms call for at peak, and how far the pump has to lift and push. This table reads the smallest Goulds 10GS model that meets each household demand at each pumping level, on a 40/60 switch.

1 bath7 gpm1½ baths10 gpm2–2½ baths14 gpm3–4 baths17 gpm
Minimum pump flow to meet a seven-minute household peak without a supplemental supply, by bathrooms (Goulds).
Pumping level1 bath (7 gpm)1½ bath (10 gpm)2–2½ bath (14 gpm)3–4 bath (17 gpm)
60 ft½ hp½ hp½ hp½ hp
100 ft¾ hp¾ hp¾ hp¾ hp
140 ft¾ hp¾ hp¾ hp¾ hp
180 ft¾ hp¾ hp¾ hp¾ hp
220 ft1 hp1 hp1 hp1 hp
260 ft1½ hp1½ hp1½ hp1½ hp
300 ft1½ hp1½ hp1½ hp1½ hp
380 ft1½ hp1½ hp1½ hp1½ hp

— means no model in the 10GS series (½ to 3 hp, recommended 3 to 16 gpm) meets that flow at that depth on 40/60; a higher-flow series is needed. Flow needs above 16 gpm sit outside the 10GS recommended range.

How to use it

Start with the pumping water level from your well log or a pump test, add the height from the wellhead to the pressure tank and the pipe friction for your run, and read the row at or below that total. The calculator does the arithmetic and draws the head. The total dynamic head guide explains each part.

The 10GS series at a glance

Each motor size covers a band of depths. The chart lists a rating only where the pump is in its recommended range, so a bigger motor is not simply "more pump" at every depth — the larger models are not rated at shallow depths at all.

ModelHPRated at 40 psiRated at 60 psi
10GS05R½20–60 ft—
10GS05½20–120 ft20–60 ft
10GS07¾40–200 ft20–160 ft
10GS10160–280 ft20–220 ft
10GS151½140–420 ft100–380 ft
10GS202200–540 ft140–500 ft
10GS303280–740 ft220–700 ft

Ratings: Goulds Water Technology, Model GS 5–25 GPM technical brochure B5-25GS (March 2012) — copy hosted by a retailer; the current Xylem brochure has no ratings tables.

Pumping level, not static level

The depth to read is where the water stands while the pump runs. A driller's log usually records both the static level and the level during a yield test; the second is the one to use. If only the static level is known, a pump test is cheaper than a pump that cannot keep up.